A bathroom can look modern, clean and properly finished while still having poor ventilation. The problem may not be obvious immediately. The exhaust fan turns on, there may be an openable window, and the bathroom appears to satisfy the basic requirements.

However, after every shower, warm moist air can remain trapped inside the room. Mirrors stay fogged, water collects on the ceiling and walls, silicone remains damp, and the shower enclosure takes far too long to dry.

Over time, this repeated moisture can create ideal conditions for mould.

Minimum compliance is only the starting point

As at August 2026, NCC 2022 Amendment 2 is the current edition of the National Construction Code applying in NSW. NCC 2025 is scheduled to be adopted in NSW on 1 May 2027. The NCC is a performance-based code that establishes minimum requirements for health, amenity, safety and sustainability. It does not necessarily provide the most effective or comfortable solution for every home.

Where mechanical exhaust ventilation is used in a Class 1 bathroom, the relevant NCC Housing Provisions specify a minimum airflow rate of 25 litres per second, equivalent to 90 cubic metres per hour. The exhaust must discharge to outdoor air through a suitable shaft or duct rather than simply releasing moist air into the roof space.

Where a bathroom does not have qualifying natural ventilation and the exhaust system does not operate continuously, the system must generally be connected to the room’s light switch and continue running for 10 minutes after the light is switched off. The room must also have an appropriate source of make-up air, commonly provided through a suitable opening beneath the door or another transfer-air opening.

These are important requirements, but minimum compliance does not guarantee that a particular bathroom will dry quickly in everyday use.

A builder may provide an openable window, a minimum-capacity fan or a centrally positioned three-in-one heat, light and exhaust unit. Such an arrangement may be compliant, but it can still leave the shower area poorly ventilated if the extraction point is too far from the main source of steam.

Why steam remains trapped around the shower

The greatest concentration of moisture is usually produced inside the shower enclosure.

Warm steam rises towards the ceiling directly above the shower. If the exhaust fan is installed near the centre of the bathroom, above the toilet or close to the doorway, much of that moisture must first escape from the enclosure and travel across the room before reaching the fan.

During that journey, it can condense on:

  • the ceiling above the shower
  • painted walls and cornices
  • grout and tile joints
  • silicone seals
  • the shower-screen frame and tracks
  • cabinetry and door surfaces
  • cold windows and mirrors

A glass shower screen can create a partially enclosed pocket of humid air. Even after the person has finished showering, water droplets remain on the glass and tiles while moisture continues circulating within the enclosure.

A weak or badly positioned fan may remove some humid air from the bathroom without properly drying the area that receives the most moisture.

Hidden mould can become an expensive problem

Visible mould on silicone or grout is unpleasant, but mould in an inaccessible part of the shower can be far more serious.

Poor ventilation by itself should not allow water to collect beneath a correctly built and properly sealed shower. However, persistent humidity can combine with failed silicone, leaking plumbing, defective screen installation, cracked grout or waterproofing problems.

Moisture may then reach concealed spaces behind shower-screen channels, beneath a framed shower base, behind wall linings or around poorly sealed junctions. These areas are dark, enclosed and difficult to dry.

Once mould develops in such a location, ordinary cleaning is unlikely to reach it. Applying new silicone over the visible surface may improve the appearance temporarily, but it does not remove contamination concealed behind or below the shower assembly.

In a serious case, proper investigation and remediation may require removal of the shower screen, shower base, wall tiles or affected wall lining. Sometimes a substantial part of the shower enclosure must be dismantled and rebuilt simply to gain access to the mould.

This is why preventing persistent moisture is usually much easier and less expensive than dealing with hidden mould after it has become established.

Ventilation is not a substitute for waterproofing

An exhaust fan cannot repair a leaking pipe, failed waterproofing membrane or defective shower base.

Where there is mould beneath or behind a shower enclosure, the cause should be investigated rather than automatically attributed to normal condensation. The bathroom may have both a ventilation problem and a water-ingress problem.

The correct approach is to identify and rectify every contributing factor. That may include improving the exhaust system, repairing failed seals, testing plumbing connections, inspecting the shower-screen installation and assessing the waterproofing where the available evidence indicates a possible failure.

Simply cleaning the mould without correcting the moisture source allows the same problem to return.

Why leaving the shower door open is not a proper solution

Leaving the shower-screen door open after use may help the enclosure dry, but it is a workaround rather than a properly designed ventilation system.

It depends on every person in the household remembering to leave the door open after every shower. That may be unrealistic in a family home or rental property.

There can also be practical safety and space problems. Many contemporary bathrooms are compact, with the shower positioned close to the vanity, toilet or entry door. A hinged shower-screen door left open may project into the only available circulation space.

Clear glass can be easy to overlook. In a narrow family bathroom, a child moving quickly through the room may collide with an open glass panel. The open door may also obstruct access to the vanity, toilet, towel rail or bathroom entrance.

A bathroom should be able to dry effectively without requiring a glass door to remain open for hours.

Capture the steam where it is produced

A more effective approach is to position the extraction point directly above the shower or as close to it as the bathroom layout and applicable electrical requirements allow.

Steam naturally rises. A ceiling-mounted exhaust fan near the shower can capture moist air before it spreads across the rest of the bathroom and condenses on other surfaces.

This does not necessarily mean installing the largest available fan. The system should be appropriately designed for the room size, shower configuration, duct route and available make-up air.

The fan and its location must also be suitable for the applicable bathroom electrical zone and installed in accordance with the manufacturer’s instructions. Electrical wiring work in NSW must be completed or supervised by a licensed electrician, with the required electrical compliance documentation provided.

In some bathrooms, a dedicated shower-zone exhaust fan can be used in addition to a centrally located heat, light and fan unit. The central unit provides general ventilation and comfort, while the dedicated fan captures the concentrated steam produced by the shower.

What makes a bathroom exhaust system effective?

Fan position

The extraction point should be located where the greatest amount of moisture is produced. For most bathrooms, that is above or immediately beside the shower enclosure, subject to electrical and product requirements.

A fan positioned near the bathroom doorway may extract some room air while allowing steam to remain concentrated above the shower.

Adequate installed airflow

The NCC minimum of 25 litres per second is a compliance baseline where mechanical exhaust is used. A larger bathroom, an enclosed shower, a long duct route or a household that takes frequent showers may justify greater capacity.

The relevant consideration is the airflow achieved by the completed system, not merely the number printed on the fan packaging. Duct length, duct diameter, bends, external grilles and other components affect how the system performs.

Correct external discharge

Bathroom exhaust should be ducted to outdoor air. Releasing warm, moisture-laden air into the roof space transfers the problem from the bathroom to a concealed part of the building, where condensation may affect timber, steel, insulation and ceiling materials.

The external outlet should be properly terminated, weather-protected and positioned so that exhausted moisture is not immediately drawn back into the home.

A sensible duct route

The duct should be correctly sized, adequately supported and kept as short and direct as reasonably practicable. Unnecessary bends, crushed flexible duct and poorly connected joints can restrict airflow.

Where condensation may form inside the duct, the design should also address the risk of water collecting or running back towards the fan.

Make-up air

An exhaust fan cannot remove air efficiently unless replacement air can enter the room.

The airflow path should be considered as a complete system: replacement air enters beneath the bathroom door or through another suitable opening, moves across the room towards the shower and leaves through the exhaust fan.

A tightly sealed bathroom door with no suitable transfer opening can restrict the fan’s performance, even when the fan motor itself is powerful.

Automatic operation

A fan that is switched off as soon as the shower ends may not have enough time to remove the remaining humidity.

A run-on timer allows the fan to continue operating after the light is switched off. A humidity sensor can provide additional control by activating the fan or extending its operation while moisture levels remain high.

Automatic control is particularly useful in family homes and investment properties because the result does not depend entirely on occupants remembering to operate the fan correctly.

Acceptable noise

A very noisy fan may technically work, but occupants may avoid using it or switch it off too early. Fan noise should therefore be considered together with airflow capacity.

A well-selected system should provide effective extraction without making normal bathroom use unnecessarily unpleasant.

Maintenance access

Dust gradually accumulates on exhaust grilles and fan components, reducing performance. The grille should be accessible for cleaning, and the duct outlet should be inspectable for obstruction or damage.

A high-capacity fan that is never cleaned may eventually perform like a much smaller unit.

Signs that bathroom ventilation may be inadequate

A bathroom does not need visible black mould before ventilation should be investigated.

Common warning signs include:

  • the mirror remaining fogged for a long time after a shower
  • droplets collecting on the ceiling or upper walls
  • paint blistering, peeling or discolouring
  • recurring mould on silicone, grout or cornices
  • a persistent musty smell
  • towels remaining damp for an unusually long time
  • rust or corrosion on metal fittings
  • swollen cabinetry or door edges
  • condensation appearing in an adjoining bedroom or hallway
  • very little noticeable air movement at the exhaust grille

A simple check is to hold a light piece of tissue near the operating grille. If there is almost no pull, the fan, duct or external outlet may require investigation. This is only an initial observation and does not measure the actual airflow rate.

Mould should not be treated as a cosmetic issue

NSW Health advises using exhaust fans when bathing and showering and opening windows when conditions permit. Mould needs moisture to grow, and controlling dampness and ventilation is an important part of prevention. People with asthma, allergies, chronic lung conditions or weakened immune systems may be more sensitive to mould exposure.

Cleaning visible mould without improving ventilation may produce only a temporary result. If the room continues to remain wet after every shower, the underlying conditions have not changed.

The objective is not merely to make the bathroom smell fresher. It is to remove moisture before it is absorbed by finishes or enters concealed parts of the building.

Why ventilation matters in an investment property

Effective, automatically controlled ventilation is particularly valuable in a rental property.

A landlord cannot assume that every tenant will open a window, leave the shower screen open or remember to run a separately switched exhaust fan after every shower. Conversely, a tenant cannot be expected to compensate indefinitely for a defective or inadequate ventilation system.

NSW rental minimum standards require adequate ventilation. NSW Fair Trading also notes that responsibility for mould may depend on how it developed, including whether the property had inadequate ventilation or whether occupants failed to use the ventilation facilities provided.

A properly positioned fan with automatic operation provides a more consistent result, reduces reliance on individual habits and may help protect bathroom finishes, cabinetry and wall linings throughout multiple tenancies.

Planning ventilation during a new build

The best time to design bathroom ventilation is before construction begins.

During a new build, the fan position can be coordinated with the shower, ceiling framing, lighting, roof structure and electrical layout. A suitable duct route and external termination can be planned before plasterboard, insulation and roof finishes restrict access.

The specification can clearly identify:

  • the fan location
  • the required airflow capacity
  • the duct diameter and route
  • the external discharge point
  • the source of make-up air
  • the switching arrangement
  • the run-on timer or humidity control
  • any separate shower-zone extraction

These details should appear in the plans, electrical schedule or inclusions rather than being left as a general note stating only that an exhaust fan will be provided.

Improving ventilation in an existing bathroom

An existing bathroom can also be upgraded.

Depending on the construction and available access, the work may include replacing an underpowered fan, adding a dedicated exhaust above the shower, correcting defective ductwork, providing a proper outdoor discharge, installing automatic controls or improving the make-up-air opening beneath the door.

The existing system should first be inspected to determine where it discharges and whether the duct is connected, damaged, restricted or blocked. In some homes, the visible ceiling grille may conceal a very small fan, disconnected duct or an arrangement that releases moisture into the roof space.

Retrofitting is generally more involved than planning the system during construction because the work may require roof-space access, new ceiling penetrations, electrical wiring, external wall or roof penetrations, plaster repairs and repainting. Nevertheless, it is usually far less disruptive than dismantling a shower later to remediate concealed moisture and mould damage.

How ARK Houses can help

Good bathroom ventilation is a small building detail with significant long-term consequences. At ARK Houses, we can plan an appropriately positioned shower-zone exhaust system as part of a new home or improve ventilation in an existing bathroom through renovation or targeted rectification. We consider fan capacity, location, external ducting, make-up air and automatic controls as one coordinated system, with the aim of removing steam before it becomes a hidden mould and maintenance problem.

Discuss Your Bathroom Project

This article provides general construction information only. Building-code requirements, fan performance, ducting, electrical zones, waterproofing and ventilation needs vary between properties and projects. Confirm the applicable requirements with appropriately licensed professionals.